SVS/12
78
994.530 G01 02
3.4.2
Connection of plastic-insulated cables
up to 630 mm2 Cu or Al via cable
socket connection
General
Plastic-insulated cables can be connected to panels up to
12 kV.
The panels are fitted with terminal blocks with locked cable
entry ports. The terminal block has three terminal strips
moulded into the cast resin insulation.
N
OTE
The termination of the cable cores and the
splitting point must comply with the cable
manufacturer's instructions.
(Crimp) cable sockets are used to connect the cable.
The maximum space for cable termination and cable
socket is
70 x 430 mm.
The maximum space available for the cable socket is
70 x 255 mm.
210
L-prof ile
210
70
Terminal
block
Cable socket
Insulat ion
conduit s
M ax. space
f or cable
f inish
430 mm
Cable
at t achment
25
5
1.