3.3.6
Connection of paper-insulated lead-
covered cables up to 240 mm
2
Cu or Al by
means of grease-filled cable boxes with
soldering gland
General
Paper-insulated lead-covered cables can be connected to load-
break switch and circuit-breaker panels up to 12 kV and to load-
break switch/fuse panels up to 12 kV. Load-break switch and
circuit-breaker panels are equipped with a terminal block with
locked cable entry ports. The terminal block has three
connection pins moulded into the cast resin insulation.
On load-break switch/fuse panels, the 12 kV connection pins are
directly below the fuse holders.
Required components
For cables with a copper core (figures 1 and 2):
one cable box (a) (depending on the core diameter)
two protection covers (c)
three cable core clamps:
d1: for core diameters
70 mm
2
d2: for core diameters > 70 mm
2
, comprising one
connecting piece, one gland and two washers with
hexagon socket head screws (figure 2)
one cable block (e)
one hose clip (f)
one gland bush (g) with O-ring
polyethylene tape
R
EMARK
For cables with an aluminium core (figure 3):
Eaton cable core clamps are only suitable for
connecting cables with a copper core.
There is a maximum free space measuring
Ø 40 x 110 mm for connecting cables with an
aluminium core by means of crimp cable
sockets, for instance.
Basically, any type of cable core clamp can be
used, provided it is within the permitted
dimensions when crimped.
1.
d2 (core diameter > 70 mm2
2.
max.
110 mm
40 mm
max.
3.
d1 (core diameter
<70 mm2)
Содержание SVS/12
Страница 133: ...SVS 12 994 530 G01 02 133 9 2 Voltage detecting system Wega 1 2...
Страница 134: ...SVS 12 134 994 530 G01 02...
Страница 135: ...SVS 12 994 530 G01 02 135...
Страница 136: ...SVS 12 136 994 530 G01 02...
Страница 137: ...SVS 12 994 530 G01 02 137 9 3 Phase monitor Orion 3 0...
Страница 138: ...SVS 12 138 994 530 G01 02...