Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
33
Table 2. Input Dry Contact Signals
External Dry Contact Signal
Basic Contractor Board
Enhanced Contractor Board
Remote EPO
Available
Available
Remote Select S1
Not Available
Switch to Source 1
Remote Select S2
Not Available
Switch to Source 2
Building Alarm 1
Name Definable
Name Definable
Building Alarm 2
Name Definable
Name Definable
Building Alarm 3
Name Definable
Name Definable
Building Alarm 4
Name Definable
Name Definable
Building Alarm 5
Not Available
Name Definable
Building Alarm 6
Not Available
Name Definable
Building Alarm 7
Not Available
Name Definable
Building Alarm 8
Not Available
Name Definable
66..33..33
R
Reem
moottee S
Soouurrccee S
Seelleecctt O
Oppttiioonn
Two external two dry contacts can be used to control the remote selection of the preferred source. Dry contact
closures are generally used when two UPSs supply power to the system. If the preferred UPS goes to bypass
mode, the “good” UPS becomes preferred:
•
Signal 1 (Remote Select S1) dry contact closure will make Source 1 preferred.
•
Signal 2 (Remote Select S2) dry contact closure will make Source 2 preferred.
•
If both dry contacts closures are open, the preferred source control is returned to the system operator
control panel.
Any remote control signal or closure puts the unit into a “Retransfer=Yes" mode to ensure system redundancy.
Normally the closures are controlled by auxiliary contacts in the UPS bypass circuit breakers. If both dry
contacts close, the first input to the STS is recognized.
66..33..44
M
Muullttii--S
Sw
wiittcchh LLiinnkk O
Oppttiioonn ((N
N++11 U
UP
PS
S))
In an N+1 UPS Configuration, there are multiple STS units, each with a preferred source fed by a separate UPS.
The alternate source on all STSs is provided by a single backup UPS.
All STS units in an N+1 UPS configuration must have Enhanced Contractor Boards and the Multi-Switch Link
Option installed, providing coordination among the STSs.
Because the backup UPS can only provide power through the STS to a single downstream load, when an STS
transfers its load to the backup UPS, the STS must signal the other STS units that it is using the UPS. The other
STS units are locked out and cannot transfer to the backup source.
An “Inhibit Transfer” alarm is signaled on each STS. The STSs are prevented from transferring until the
Preferred Source on the STS using the backup UPS returns to normal and the STS retransfers the load back to
the Preferred Source.
Содержание STS 2000A
Страница 1: ...p n 164001127 Revision 01 Installation and Operation Manual Eaton Static Transfer Switch 2000A 3 Pole...
Страница 8: ......
Страница 16: ...xvi Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 List of Tables...
Страница 32: ...16 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Safety...
Страница 98: ...82 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Troubleshooting...
Страница 120: ...16400112701 164001127 01...