Technical Specification SPD3200-TN-E 

 Doc# 5100SPD3200TNE 

Page 1 of 2 

 
 

 

T

ECHNICAL 

S

PECIFICATION AND 

INSTALLATION GUIDE

 

SPD3200-TN-E  

PRIMARY

 

SURGE

 

DIVERTER 

( IEC61643-11 Class I & II, 200kA, 3 phase, All 

mode, 380-440vac ) 

APPLICATIONS 

 

Primary power circuits 

 

Telecommunication Systems / Rectifiers 

 

Process and Control Systems  

 

Computer Systems / Medical Systems 

FEATURES 

 

Compact 3 phase, panel mount metal 
enclosure

 

 

Includes 3 phase MCB safety disconnect 
housed inside enclosure.

 

 

200kA L-E each phase

100kA N-E  

 

 

Dry contact alarm outputs 

 

LED  visual indicators for protection  and 
power 

 

Integrated surge counter visible from 
front panel. 

 

FUNCTIONAL DESCRIPTION 

 The  SPD3200-TN-E  is  designed  to  protect  three 
phase  power  systems  against  damage  from  surges 
and  spikes  caused  by  lightning  and  other  electrical 
sources.  The  unit  is  intended  for  point  of  entry  or 
main  board  protection  and  is  connected  in  parallel 
with  the  power  system  via  its  own  safety  disconnect 
MCB.  
Differential  and  common  mode  transients  are 
diverted  to  mains  earth  via  internally  mounted  surge 
diverters  through  a  common  earth  bus.  All  internal 
connections are designed for minimum impedance to 
enable maximum current flow back to earth. 
  

This model ( SPD3200-TN-E ) is designed for use 
in  systems  with  a  grounded  neutral  where 
connected  for  N-E  operation.  Line  transients  are 
diverted directly in L-E mode. 
 

 

OPERATION 

Indicators  -  The  operation  status  of  the  SPD3200  is 
indicated by blue indicators on the front panel. These 
4  indicators  show  the  status  of  each  of  the  L  and  N 
surge  diverters  inside  the  unit.  The  indicators  are 
blue  when  the  unit  is  powered  on  and  operating. 
When  any  of  these  extinguishes  then  the 
corresponding  internal  surge  diverter  should  be 
replaced.  When  any  indicator  fails  the  protection 
relay  contacts  change over.  The power failure alarm 
will  also  operate  when  mains  voltage  falls  below 
180VAC. 
External  safety  disconnector  -  The  prescribed  safety 
disconnector  is  provided  as  part  of  the  unit  and  is  a 
63A  MCB  specially  tested  for  this  application.  This 
MCB  is  mounted  on  the  inside  of  the  unit  and  is 
where all connections are made. 
Surge  counter  -  The  unit  comes  with  a  LCD  display 
surge  counter.  The  counter  will  operate  each  time 
there is a current pulse event occurring between L-E 
and  has  a  threshold  trigger  level  of  <1.5kA.  Each 
event will cause the counter to increment. 
Key  lock    -  The  unit  comes  with  a  key  lock  on  the 
front panel to prevent uncontrolled access. 
Cable entry – L and N connections are made through 
a  separate  cable  gland  entry  point  at  the  top  left  of 
the  unit.  Earth  connections  can  be  made  via  a 
separate  cable  gland  connection  also  on  the  top  of 
the unit. 
 

 