SmartWire-DT network
23
02/11 MN05006002Z-EN
SmartWire-DT station address assignment
To operate a SmartWire-DT network, addresses must be
assigned to the SmartWire-DT slaves. Addresses must be
assigned during commissioning, on any changes in configu-
ration and when replacing slaves. To assign addresses, press
the Config. key on the SmartWire-DT gateway. After address
assignment, all found stations are saved in the gateway’s
target configuration.
The configuration state is indicated by the SmartWire-DT
LED:
Preconditions for address assignment:
The gateway has a connection to the SmartWire-DT network
when its supply voltage is first switched on; the field bus
plug is disconnected.
Pressing the Config. key for at least two seconds starts auto-
matic address assignment.
The SmartWire-DT gateway reports this status with the
following LED indication:
SWD-LED
Status
Red flashing
No target configuration present
(for initial startup)
Green
Target configuration present
h
Pressing the Config. key when switching on the gateway
will switch it to “Firmware update“ mode.
Automatic address assignment to the SmartWire-DT
slaves is not possible in this state.
An operating system update can be performed with design
software SWD-Assist. For further information, see manual
MN05013002Z-EN, “SmartWire-DT Gateway”.