Commissioning
100
02/11 MN05006002Z-EN
Creating a target configu-
ration
Before the SmartWire-DT gateway can exchange data with
the PLC, it must store the found configuration of the Smart-
Wire-DT slaves internally as a
target configuration
.
X
Press the “Config.” pushbutton actuator for at least two
seconds.
The SmartWire-DT gateway stores the found configuration
internally as a target configuration. With the aid of this
target configuration the SmartWire-DT coupling unit checks
each time the voltage supply is retriggered on whether the
number and part no. of SmartWire-DT slaves present on the
SmartWire-DT network are unchanged and whether the
SmartWire-DT topology is functional with these.
Status messages of the SmartWire-DT gateway after
creating the target configuration
Table 13:
LED indication of the SmartWire-DT gateway after
creating the target configuration
For the connected SmartWire-DT slaves the status LED for
diagnosis of the SmartWire-DT network lights up continu-
ously green.
h
The function of the “Config.” pushbutton is disabled as
long as communication with the field bus master is active.
If necessary, interrupt communication by pulling out the
field bus plug. While the SmartWire-DT coupling unit is
determining the configuration, the SmartWire-DT LED
flashes in the colour orange, frequency (1 Hz). For the
connected SmartWire-DT slaves the status LED for diag-
nosis of the SmartWire-DT network flashes in the colour
green, frequency (1 Hz).
LED
Status
SWD
Green continuous light
Config.
Off (no planned configuration is available)
www.comoso.com