SC200 Setup
The network administrator must assign a unique IP address to each SC200 to be connected to the
TCP/IP network.
► To configure an SC200 for Ethernet communications from the keypad
Go to
Settings
>
Setup
Enter the
IP Address
,
Subnet Mask
and
Gateway Address
assigned by the network
administrator.
If required, set
HTTP Access
to
Enabled
for web browser access, or set
HTTPS Access
to
Enabled
for secure web access.
► To configure an SC200 for Ethernet communications using
DCTools
Connect using USB (see details on page
In DCTools go to
Configuration
>
Communications
.
Under
Ethernet
, type the
IP Address
,
Subnet Mask
and
Gateway Address
assigned by the
network administrator.
If required, under
HTTP (Web)
, set
HTTP Access
to
Enabled
for web browser access, or set
HTTPS Access
to
Enabled
for secure web access.
DCTools or PowerManagerII Communications Setup (if required)
► To connect to the SC200 with DCTools or PowerManagerII:
1
Install DCTools/PowerManagerII on the PC/laptop.
2
Double-click the DCTools/PowerManagerII icon to open the connection manager.
3
Go to
Connection
>
New
to open a new connection dialog box.
4
Enter:
Connection Name: <as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Ethernet
S3P Address:
0
(
0 = Broadcast, 1-65279 = individual address
)
Server IP Address: Allocated by network administrator
Server Port:
Allocated by network administrator
Telnet
Cleared
5
Press OK. DCTools/PowerManagerII will now connect to the SC200.
6
See System Operation on page
for details of the SC200 control and monitoring functions
available via DCTools.
For help using DCTools press F1.
7
If required, access to the SC200 via DCTools or PowerManagerII can be password
controlled. See Write Access Password on page
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...