![Eaton SC200 Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/eaton/sc200/sc200_operation-handbook_3771908046.webp)
SC200 Handbook
38
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50H November 2011
Factory-fitted contactors will be characterized at the factory. If an existing contactor is replaced,
characterize the new contactor from the SC200.
In this case, there will be no LVD Characterization Error alarm.
To characterize the new contactor, go to
Battery
, go to the
LVDs
tab, select the appropriate
LVD channel and press
Details
, select the appropriate contactor and press
Edit,
select
Characterization
and press
Enter
, select
Characterize Contactor
and press
Start
.
* LVD Characterization is only available for LVD contactors with auxiliary contacts. If auxiliary
contacts are not fitted then the nominal LVD coil voltage must equal the dc power system nominal
bus voltage. See LVD Specifications on page
LVD Operation
► To allow access to LVD functions from the SC200 keypad
In DCTools/Web go to:
Control Processes
>
LVD
.
Select the
Allow Front Panel LVD Control
check box.
If the check box is cleared LVD functions can only be accessed using DCTools/Web.
► To manually connect or disconnect an LVD control channel
Use the SC200 keypad to go to:
Battery > LVDs
>
LVD 1 - LVD 16
>
Details
>
Manual Control.
Select
Connect or Disconnect
to connect or disconnect the channel (and all mapped
contactors).
The contactor(s) will remain in the selected state until another state or Auto is selected.
Select
Auto
to return the LVD control channel to automatic operation.
Содержание SC200
Страница 4: ......
Страница 8: ......
Страница 28: ...SC200 Handbook 20 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 88: ...SC200 Handbook 80 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 116: ...SC200 Handbook 108 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 120: ...SC200 Handbook 112 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 130: ...SC200 Handbook 122 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...
Страница 134: ...SC200 Handbook 126 Copyright 2007 2011 Eaton Corporation All Rights Reserved IPN 997 00012 50H November 2011...