I
Batteries
•
Batteries can present a risk of electric shock or burns from high short-circuit current.
•
Do not alter any battery module cables or connectors.
•
Do not place any metal objects in or near the connectors.
•
VRLA lead acid batteries can emit explosive gases and must be installed with adequate
ventilation. Do not install batteries in a sealed room or cabinet.
•
Do not attempt to disassemble battery modules. Return them (in their original packaging) with a
completed Equipment Incident Report on page
.
•
Only dispose of battery modules according to Battery Disposal and Recycling on page
•
Check the battery recharge dates on the shipping carton labels. Do not use the batteries if the
date has expired and the batteries were never recharged. Contact your battery supplier.
•
Batteries are heavy. Two people may be required to lift a module.
•
Batteries must be installed at the bottom of the rack.
Inspecting the Equipment and Reporting Damage
Unpack the equipment and inspect it carefully for possible damage that may have occurred
while in transit. Do not use any damaged equipment.
Report any damage immediately, using a completed Equipment Incident Report on page
Keep the original packaging and use it if any equipment needs to be returned for replacement or
repair.