10 Parameter list
10.4 Parameter groups for RASP
172
Rapid Link 5 · RAMO5 · RASP5
10/19 MN034004EN
www.eaton.com
10.4 Parameter groups for RASP
10.4.1 “Monitor” parameter group 0
Parameter
Designation
Description
Unit
P0-02
Thermistor Input1
Thermistor Status
0: Motor temperature ok
1: Motor temperature too high
P0-03
DI Status
Status of the Sensor Inputs and ASI Pin 4
P0-04
f-PreRamp
Speed reference in front of the ramp
Hz/rpm
P0-05
T-Controlboard
Internal ambient temperature of the device, measured on the
control board
°C
P0-06
Overload
Calculated overload in % above the currentlevel set with P1-08.
If the value rises to 100 %, the device will trip with error
message
I.t-trP
.
%
P0-07
Output Frequency
Instantaneous output frequency
Hz/rpm
P0-08
Motor Speed
Motorspeed (calculated or measured)
Hz/rpm
P0-09
Motor Current
Instantaneous output current
A
P0-10
Motor Power Rel
Motor Power (actual value) in kW/HP
kW
P0-11
Motor Voltage
Instantaneous output voltage
V
P0-12
Motor Torque
Motor-Torque
Display 1000
≙
100 %
%
P0-13
Trip Log
Display of the 4 latest faults
P0-14
Magnetizing current Id
Calculated Magnetizing Current
(I
d
), providing an autotune has successfully been completed.
A
P0-15
Torque current Iq
Calculated Torque producing Current
(I
q
), providing an autotune has successfully been completed.
A
P0-16
DC-Link Voltage Ripple
DC-Link Voltage Ripple
V
P0-17
HOA Status
Key switch status
1 hand
2: auto
P0-18
FWD/REV Status
Selector switch status FWD / REV
1: FWD
2: REV
P0-19
DO 1 to 3 Status
Status of the actuators
P0-20
DC-Link Voltage
Instantaneous DC Link Voltage
Display 600 = 600 V
V
P0-21
Heatsink Temperature
Instantaneous Heatsink Temperature
Display 40 = 40 °C
°C
P0-22
TimeToNextService
Time remaining to next service
The service interval is set with P2-28.
Hours
P0-23
t-Run IGBT in OT
Time elapsed, in which the drive has operated with a high heat-
sink temperature
Displays the time in hours and minutes above 85 °C.
The value is used for various internal protective functions.
hh:mm:ss
Содержание Rapid Link RAMO5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN ...
Страница 4: ...II ...
Страница 10: ...6 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 122: ...4 Operation 4 3 Manual control 118 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 136: ...5 RAMO5 Motor starter 5 7 Configure special settings 132 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 158: ...8 PC tool 8 2 Parameter Editor 154 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 164: ...9 Control Unit 9 2 Extended parameter set 160 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 194: ...10 Parameter list 10 4 Parameter groups for RASP 190 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 208: ...11 Communications 11 5 OP Bus 204 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...
Страница 216: ...12 Error messages 12 3 RASP Error list 212 Rapid Link 5 RAMO5 RASP5 10 19 MN034004EN www eaton com ...