1 Rapid Link 5 system
1.6 Selection criteria
28
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
1.6 Selection criteria
Select a RAMO5 or RASP5
③
device according to the supply voltage U
LN
of
the supply system
①
and the rated current of the assigned motor
②
.
The circuit type (
Δ
/
) of the motor must be selected for the supply voltage
①
.
The RASP5 unit’s rated output current I
e
must be greater than or equal to the
rated motor current. For RAMO5, current monitoring must be set to the
rated motor current.
Figure 7:
Selection criteria
When selecting the drive, the following criteria must be known:
•
Type of motor (three-phase asynchronous motor)
•
Mains voltage = rated operating voltage of the motor (e.g. 3 AC ~ 400 V),
•
Rated motor current (recommended value, dependent on the circuit type
and the supply power supply)
•
Load Torque,
•
Starting torque,
•
Ambient temperature.
ATTENTION
Do not disconnect or connect power connectors (mains, motor)
while RAMO5 and RASP5 are operational.
230 / 400 V ∆ /
4.6 / 2.6
1.1
0.81
ϕ
cos
kW
min
-1
1430
50 Hz
A
②
①
U, I, f
③
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...