8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
181
8.4.3 Parameter group 2 (Extended functions)
Table 42:
Parameter group 2 (Extended functions)
Parameter
Designation
Description
Unit
Min
Max
DS
P2-01
f-Fix2
Preset Fixed Frequency 2
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm
P1-02
P1-01
30 Hz
P2-02
f-Fix3
Preset Fixed Frequency 3
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm
P1-02
P1-01
40 Hz
P2-03
f-Fix4
Preset Fixed Frequency 4
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm
P1-02
P1-01
50 hz
P2-04
f-Fix5
Preset Fixed Frequency 5
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm
P1-02
P1-01
10 hz
P2-05
f-Fix6
Preset Fixed Frequency 6
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm
P1-02
P1-01
15 Hz
P2-06
f-Fix7
Preset Fixed Frequency 7
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm
P1-02
P1-01
20 hz
P2-07
f-Fix8
Preset Fixed Frequency 8
Value can be adjusted between f-min and f-max.
Selection via a digital control signal.
Hz/rpm
P1-02
P1-01
25 Hz
P2-08
t-SRamp1
Curve shape, temporal S-shape
Linear acceleration and deceleration time according to P1-03
and P1-04.
Timed slurred Transition to Start and End of Acceleration
(P1-03) and Deceleration Ramps (P1-04).
The time set here applies for both ramps.
0.0 = linear
s
0
10
0
P2-09
Overvoltage control
The overvoltage control prevents the drive from tripping in
case of regenerative energy feedback from the motor to the
DC link.
When disabled, the drive will trip “Over Voltage” instead of
automatically increasing the motor ramp times.
-
0
1
1
P2-10
REV Enable
Activates or deactivates reverse rotation of the motor
0: 0: REV activated - motor is running forward and in reverse
1: REV deactivated - motor will only run forward
-
0
1
0
P2-11
t-acc2
Sets the acceleration ramp time 2 in seconds
s
0
3000
5.0
P2-12
n-accMulti1
Frequency / speed, at which the acceleration ramp changes
from t-acc1 to t-acc2.
This can be set to any value between 0 and “f-max” (P1-01)
“Motor Nom Speed” (P1-10) = 0, displayed in Hz.
“Motor Nom Speed” (P1-10) > 0, displayed in rpm.
Frequency / Speed > P2-12 = t-acc2
Frequency / Speed < P2-12 = t-acc1
Hz/rpm
0
P1-01
0
P2-13
t-dec2
Sets the deceleration ramp time 2 in seconds.
Activation via pin 4 at AS-i.
s
0
3000
5.0
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...