8 Parameter list
8.4 Parameter groups for RASP5
Rapid Link 5 · RAMO5 · RASP5
05/20 MN034004EN
www.eaton.com
175
8.4 Parameter groups for RASP5
8.4.1 Parameter group 0 (Monitor)
Table 40:
Parameter group 0 (Monitor)
Parameter
Designation
Description
Unit
P0-02
Thermistor input1
Thermistor status
0: Motor temperature OK
1: Motor temperature too high
–
P0-03
SEN Status
Status of the sensor inputs and ASI pin 4
–
P0-04
f-PreRamp
Speed reference in front of the ramp
Hz/rpm
P0-05
T-Controlboard
Internal ambient temperature of the device, measured on the control board
°C
P0-06
Overload
Calculated overload in % above the current level set with P1-08. If the value
rises to 100 %, the device will trip with error message “iT-Trp”.
%
P0-07
Output frequency
Instantaneous output frequency
Hz/rpm
P0-08
Motor speed
Motor speed (calculated or measured)
Hz/rpm
P0-09
Motor current
Instantaneous output current
A
P0-10
Motor Power Rel
Motor Power (actual value) in kW/HP
kW
P0-11
Motor voltage
Instantaneous output voltage
V
P0-12
Motor torque
Motor torque
Display: 1000
≙
100%
%
P0-13
Trip Log
Display of the 4 latest faults
P0-14
Magnetizing current I
d
Calculated magnetizing current I
d
– providing an autotune has been completed successfully.
A
P0-15
Torque current I
q
Calculated torque-producing current I
q
– providing an autotune has been completed successfully.
A
P0-16
DC-Link Voltage Ripple
DC-Link Voltage Ripple
V
P0-17
HOA status
Key switch status
1: Hand
2: Auto
P0-18
FWD/REV status
Selector switch status FWD / REV
1: FWD
2: REV
P0-19
DO 1 to 3 Status
Status of the actuators
P0-20
DC-Link voltage
Instantaneous DC Link Voltage
Display: 600
≙
600 V
V
P0-21
Heatsink temperature
Instantaneous Heatsink Temperature
Display: 40
≙
40 °C
°C
P0-22
TimeToNextService
Time remaining to next service (in hours).
The service interval is set with P2-28.
Hours
P0-23
t-Run IGBT in OT
Time elapsed, in which the drive has operated with a high heatsink
temperature
Displays the time in hours and minutes above 85 °C.
The value is used for various internal protective functions.
hh:mm:ss
Содержание Rapid Link 5
Страница 1: ...Manual Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN ...
Страница 4: ...II ...
Страница 38: ...1 Rapid Link 5 system 1 10 Service and warranty 34 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 118: ...3 Installation 3 7 Isolation test 114 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 196: ...8 Parameter list 8 4 Parameter groups for RASP5 192 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...
Страница 246: ...10 Error Messages 10 2 Error Messages 242 Rapid Link 5 RAMO5 RASP5 05 20 MN034004EN www eaton com ...