Eaton PXBCM-DISP-6-XV Скачать руководство пользователя страница 1

For detailed information concerning the operation and features avail-

able in the PXBCM meter display - 6” color touchscreen (PXBCM-

DISP-6-XV or PXBCM-DISP-6-TM-XV), please refer to PXBCM meter 

color touchscreen display features (IB150023EN) or PXBCM meter 

tenant meter touchscreen display features (IB150030EN) available on 

the Eaton website (www.eaton.com/meters).

Figure 1. Color touchscreen display for PXBCM series meter.

Technical information

• 

640 x 480 pixel backlit VGA touch screen display.

• 

Power: 24 Vdc input.

Effective November 2020
Supersedes June 2019

Technical Data 

TD150031EN

PXBCM meter color touchscreen 

display quick start guide

Display measurements

• 

Height: 5.24 in. (133 mm);

• 

Width: 6.81 in. (173 mm);

• 

Depth: 1.54 in. (39 mm);

• 

Weight: 1.32 lb (600 g);

• 

Cutout dimensions: 4.61 in. x 6.18 in.(117.0 x 157.0 mm).

Ratings

• 

Front bezel IP rating: IP65;

• 

Operating temperature: 0 ~ 50°C (32 ~ 122°F);

• 

Storage temperature: -20 ~ 60°C (-4 ~ 140°F);

• 

Ambient humidity: 10% ~ 90% RH (0 ~ 40°C [32 ~ 104°F]),  

10% ~ 55% RH (41 ~ 50°C [105.8 ~ 122°F]).

Figure 2. Dimensions of the PXBCM meter display - 6” color 

touchscreen (PXBCM-DISP-6-XV).

Содержание PXBCM-DISP-6-XV

Страница 1: ...formation 640 x 480 pixel backlit VGA touch screen display Power 24 Vdc input Effective November 2020 Supersedes June 2019 Technical Data TD150031EN PXBCM meter color touchscreen display quick start guide Display measurements Height 5 24 in 133 mm Width 6 81 in 173 mm Depth 1 54 in 39 mm Weight 1 32 lb 600 g Cutout dimensions 4 61 in x 6 18 in 117 0 x 157 0 mm Ratings Front bezel IP rating IP65 Op...

Страница 2: ...Cut out the marked area Figure 3 Cut out dimensions 4 Insure proper gasket placement on the PXBCM meter color touchscreen display 5 Insert the PXBCM meter color touchscreen display through the cutout 6 Fit the supplied threaded pins in the retaining brackets The tips of the threaded pins must point towards the wider ends of the retaining brackets Clip on the retaining brackets in the recesses prov...

Страница 3: ... 1 or 2 RS485 of the PXBCM meter base For best results use the default communication settings for the PXBCM color touchscreen display 38 4 kbps 1 start bit 1 stop bit no parity In applications requiring both COM ports COM 2 is rec ommended for the display ote N By default the PXBCM color touchscreen display is preset for a PXBCM meter base Modbus address of 01 To accommodate a different Modbus add...

Страница 4: ...he firmware update file from eaton com Save to the PC Unzip the folder 2 Press the CTRL button on the right side of the display to exit the application 3 On the display select Start Settings Network and Dial up Connections Double click ONBOA to see the Display s Ethernet connection IP address Verify that this is 192 168 1 1 If it is not edit the fields and click OK 4 Attach Ethernet cable between ...

Отзывы: