86-87050-00 A02 - Page 29
5. Troubleshooting
Displayed details
Signification
Correction
NO BATTERY
The battery is incorrectly
connected
Check battery connections (see section 2.9)
I/O BAD CONNECTION
AC source is not connected to the
correct terminals
Check AC wiring
NO POWER MODULE
The power sub-module is not
inserted
Check power sub-module connections
(see section 7.1)
NO BATTERY MODULE
The battery sub-module is
incorrectly connected
Check battery connections
(see section 7.2)
INV THERM OVERLOAD
The UPS shuts down automatically
because of a major overload
Check the power drawn by the connected
devices and disconnect any non-priority
devices
INVERT LIMITATION
Short circuit conditions on output
devices
Check the installation at the UPS output
(wiring, fault equipment)
5.1 Troubleshooting LEDS (21) and (22)
If LED
(21)
is ON:
The equipment is protected by the UPS but the
operation is downgraded.
If LED
(22)
is ON:
The equipment is no longer protected by the UPS.
5.2 Troubleshooting Not Requiring EATON After-Sales Support
27
ENVIRONMENT FAULT
Press the “Enter” button
(27)
to display the details below:
Содержание Pulsar EX RT 5000
Страница 2: ......
Страница 4: ......
Страница 10: ...86 87050 00 A02 Page 8 This page left blank intentionally...
Страница 30: ...86 87050 00 A02 Page 28 This page left blank intentionally...
Страница 34: ...86 87050 00 A02 Page 32 This page left blank intentionally...
Страница 36: ...86 87050 00 A02 Page 34...
Страница 38: ...86 87050 00 A02 Page 36...
Страница 40: ...86 87050 00 A02 Page 38...
Страница 42: ...Notes 86 87050 00 A02 Page 40...
Страница 43: ...86 87050 00 A02...
Страница 44: ...www eaton com 86 87050 00 A02...