3 Installation
3.5 EMC installation
60
DC1-S…20…, DC1-S…OE1 Variable Frequency Drives
05/21 MN040058EN
www.eaton.com
3.5.4 Screen earth kit
Cables that are not screened work like antennas (sending, receiving).
The effectiveness of the cable screen depends on a good screen connection
and a low screen impedance.
→
For a proper EMC connection, cables emitting interference
(e.g. motor cables) and susceptible cables (analog signal and
measured values) must be screened and laid separately from
each other.
→
Use only screens with tinned or nickel-plated copper braiding.
Screens made of steel braids or metal conduits are either not
suitable or suitable only to a limited extent (depending on the
EMC environment).
→
Control and signal lines (analog, digital) should always be
grounded on one end, in the immediate vicinity of the supply
voltage source (PES).
Содержание PowerXL
Страница 4: ......
Страница 124: ...5 Operation 5 7 Handling the keypad 120 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...
Страница 160: ...6 Parameter structure 6 7 Fault messages 156 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...
Страница 170: ...7 Technical Data 7 3 Dimensions 166 DC1 S 20 DC1 S OE1 Variable Frequency Drives 05 21 MN040058EN www eaton com...