Specification are subject to change without notice. Copyright 2005 Eaton Power Quality Pty Ltd 

Technical Specification – SPD3Gi/A 

Tvss Doc# 510075 

Page 1 of 2 

 

Web: 

http://www.powerware.com.au

 Phone: 1300 UPS UPS

 

SPD3Gi/A S

URGE 

D

IVERTER

 

(3 Phase, 380-520V, 40kA per mode) 

INSTALLATION INSTRUCTIONS 

FEATURES 

• 

Extended voltage range 

• 

Common-earth protection (L-E, N-E) 

• 

Compact solution for 3-phase protection 

• 

DIN43880 case, 35 mm DIN-rail mountable 

• 

All MOVs thermally protected 

• 

Includes dry-contact alarm

 

Applications 

• 

Secondary power circuits / Sub-boards 

• 

Telecommunication Systems / Rectifiers 

• 

Process and Control Systems / Homes & Units 

• 

Computer Systems / Medical Systems 

• 

All sensitive Electronic Equipment

 

FUNCTIONAL DESCRIPTION  

The SPD3i is designed to protect 3-phase power 
systems against damage from surges and spikes 
caused by lightning and other electrical sources. The 
unit is intended for point-of-entry or sub-board 
protection and is connected in parallel with the power 
system via HRC fuses. This unit is available in 
various models for different voltages and 
applications. Check that the model you have 
purchased is rated correctly for your power system. 

This model (SPD3Gi/A) is designed for TN-S and 
TT power systems in the range of 220-300V(380-
520V). If your power system is TN-C, TNC-S or IT, 
or of a different voltage, this model is NOT 
suitable

.  

 
Please contact your supplier for a suitable model to 
suit your application. 

 
OPERATION 

Two lamps on the front panel indicate the operation 
status of the unit. The ‘OK’ lamp indicates that power 
is applied to the unit and the ‘FAULT’ lamp indicates 
reduced protection. If the ‘FAULT’ lamp is lit it is likely 
that the unit is damaged and must be replaced. If the 
breaker/fuse is intact and power is definitely being 
supplied through the unit (check with meter) but the 
‘OK’ lamp doesn’t light then the unit is faulty and 
must be replaced.

  

 

WARRANTY

  

Eaton Power Quality warrants this unit against faulty 
parts and workmanship for a period of 12 months 
from the date of purchase. If this product fails to 
operate correctly, please contact your Eaton 
representative. This warranty doesn’t cover neglect 
or intentional misuse. As this product is intended for 
use in electrically harsh environments no claim is 
made of suitability for purpose. This unit is designed 
to reduce the likelihood of damage, not prevent it. 
Please also note that an excessive surge, such as 
from a direct lightning strike to the site or a power 
system fault, may cause damage to the unit and 
render it inoperable. A unit that has been damaged in 
this way is not warrantable. 

 

 

 
 

For installation details,  

see over page. 

SPECIFICATIONS

 

Manufacturers name and model 

Eaton Powerware 
SPD3Gi/A 

Method of mounting 

Fixed. DIN Rail mount 

Input voltage 

220-300VAC (380-520V) 
40-70Hz 

Maximum continuous operating 
voltage - MCOV 

350VAC 

Temporary over-voltage – TOV 

420VAC, 15 mins 

Service type 

TN-S and TT (3-wire with 
grounded neutral) 

Test classification  

Class II 

Supply current 

50mA 

Initial clamp voltage 

680V 

Maximum rated surge current - 
Ismax 8/20us  

40kA 

Nominal surge current - In 
8/20us 

20kA 

Residual voltage (Vpl) @  
3kA, 8/20uS 

1.2kV L-E 

≤1

.4KV N-E 

Residual voltage (Vpl) @ Ismax 
40kA, 8/20uS 

2.1Kv L-E 

2.45KV N-E  

Energy absorbtion (2ms) 

3640j 

Nominal surge lifetime (In) 

20kA (8/20uS), 20 times 

Internal protection (fusing) 

MOV thermal fuses 135

°

External disconnector 
requirements 

Gg/Gl HRC fuses, 1 per 
phase, 125A maximum.

 

Terminations 

Power terminals 16mm

2

 , 

Alarm terminals 1.5mm

2

 

Alarms/indicators 

5 indicators, dry contact 
alarm relay  – 
250VAC/32VDC, 5A 

Location Category 

Indoor 

Enclosure rating 

IP20 

Applicable standards. 

IEC61643-1, IEC610006, 
ANSI/IEEE C62.41, 
AS1768-2003, AS3100  

Dimensions 

DIN43880, 4 units (70mm) 

Weight 

200g 

Environment 

-10 to 60C, 0-90%RH 

Warranty 

12 months, workmanship 
and materials 