Technical Specification –SPD120i/A
Tvss Doc# 510077
Page 1 of 2
Web:
http://www.powerware.com.au
Phone: 1300 UPS UPS
SPD120i/A S
URGE
D
IVERTER
(Single mode, 220-277V (380-480V), 100kA)
INSTALLATION INSTRUCTIONS
FEATURES
•
1 mode protection (L-N or L-E)
•
Compact solution for primary protection
•
DIN43880 case, 35 mm DIN-rail mountable
•
All MOVs thermally protected
•
Includes dry-contact alarm
Applications
•
Mains point-of-entry /Main SWB
•
Telecommunication Systems / Rectifiers
•
Process and Control Systems / Factories & Units
•
Computer Systems / Medical Systems
•
All sensitive Electronic Equipment
FUNCTIONAL DESCRIPTION
The SPD120i is designed to protect single and 3-
phase power systems against damage from surges
and spikes caused by lightning and other electrical
sources. The unit is intended for point-of-entry or
main-board protection and is connected in parallel
with the power system via HRC fuses. This unit is
available in various models for different voltages and
applications. Check that the model you have
purchased is rated correctly for your power system.
.
This model (SPD120i/A) is designed for single
and 3-phase power systems, with a grounded
neutral, in the range of 220-277V(380-480V). If
your power system is “delta” (i.e. ungrounded),
or of a different voltage, this model is NOT
suitable
.
Please contact your supplier for a suitable model to
suit your application.
OPERATION
Two lamps on the front panel indicate the operation
status of the unit. The ‘OK’ lamp indicates that power
is applied to the unit and the ‘FAULT’ lamp indicates
reduced protection. If the ‘FAULT’ lamp is lit it is likely
that the unit is damaged and must be replaced. If the
breaker/fuse is intact and power is definitely being
supplied through the unit (check with meter) but the
‘OK’ lamp doesn’t light then the unit is faulty and
must be replaced.
WARRANTY
Eaton Power Quality warrants this unit against faulty
parts and workmanship for a period of 12 months
from the date of purchase. If this product fails to
operate correctly, please contact your Eaton
representative. This warranty doesn’t cover neglect
or intentional misuse. As this product is intended for
use in electrically harsh environments no claim is
made of suitability for purpose. This unit is designed
to reduce the likelihood of damage, not prevent it.
Please also note that an excessive surge, such as
from a direct lightning strike to the site or a power
system fault, may cause damage to the unit and
render it inoperable. A unit that has been damaged in
this way is not warrantable.
For installation details,
see over page.
SPECIFICATIONS
Manufacturers name and model
Eaton Powerware
SPD120i/A
Method of mounting
Fixed. DIN Rail mount
Input voltage
220-277VAC (380-480V)
40-70Hz
Maximum continuous operating
voltage - MCOV
320VAC
Temporary over-voltage – TOV
350VAC, 15 mins
Service type
TN-C and TN C-S (3-phase
with grounded neutral)
Test classification
Class II
Supply current
50mA
Initial clamp voltage
560V
Maximum rated surge current -
Ismax 8/20us
100kA
Nominal surge current - In
8/20us
50kA
Residual voltage (Vpl) @
3kA, 8/20uS
1.0kV
Residual voltage (Vpl) @
40kA, 8/20uS
1.65kV
Residual voltage (Vpl) @ Ismax
100kA, 8/20uS
2.5KV
Energy absorbtion (2ms)
2130j
Nominal surge lifetime (In)
50kA (8/20uS), 20 times
Internal protection (fusing)
MOV thermal fuses 135
°
C
External disconnector
requirements
Gg/Gl HRC fuses, 1 per
phase, 125A maximum.
Terminations
Power terminals 16mm
2
,
Alarm terminals 1.5mm
2
Alarms/indicators
5 indicators, dry contact
alarm relay –
250VAC/32VDC, 5A
Location Category
Indoor
Enclosure rating
IP20
Applicable standards.
IEC61643-1, IEC610006,
ANSI/IEEE C62.41,
AS1768-2003, AS3100
Dimensions
DIN43880, 4 units (70mm)
Weight
200g
Environment
-10 to 60C, 0-90%RH
Warranty
12 months, workmanship
and materials