INSTALLATION
Eaton 9390 UPS, 9395 UPS, and 9395 SSBM Sync Control Installation and Operation Manual
S
P-164000052 Rev 2
3-8
3.2
Installation and Wiring with an Eaton 9395 UPS
NOTE
When installing wiring connections, conduit must be installed between the Eaton Sync Control and the
UPS cabinet.
To install and wire:
1.
Install the Eaton Sync Control panel to the selected mounting location.
See Figure 2‐1 on page 2-2 for mounting hole dimensions and Figure 2‐2 on
page 2-3 for conduit entrance locations.
2.
Unfasten the front door latches and swing the door open.
3.
Complete all control wiring interconnections using Table 3‐2 for wiring
requirements.
Figure 3‐1 shows the Eaton Sync Control TB1 terminal block and ground terminal
locations. Figure 3‐2 shows the TB1 terminal block wiring detail.
Figure 3‐7 through Figure 3‐10 show the typical locations of the UPS TB3, TB6,
and X-Slot
®
Communication bays. Figure 3‐5 shows the TB6 detail.
Refer to the applicable Eaton 9395 UPS Installation and Operation Manual listed
in paragraph 1.3 on page 1-4 for UPS cabinet terminal locations and assignments,
termination requirements, conduit landing locations, and terminal access
instructions.
NOTE
Complete the wiring to the X-Slot Relay Interface Card or Industrial Relay Card terminals before
installing the cards in the Communication Bay in each of the UPS cabinets.
4.
Route wires through the strain relief bushing and connect to the terminals on the
X-Slot Relay Interface Card in each of the UPS cabinets (see Figure 3‐13).
5.
Install the X-Slot Relay Interface Card or Industrial Relay Card into an open X-Slot
communication bay on the front of the UPS (see Figure 3‐7, Figure 3‐8,
Figure 3‐9, or Figure 3‐10). Refer to the applicable Eaton 9395 UPS Installation
and Operation Manual listed in paragraph 1.3 on for UPS cabinet access
instructions.
6.
Verify the jumper is installed between Sync Control terminal TB1-40 and TB1-41
(see Figure 3‐2).
7.
When all wiring is complete, close the door and secure the latch.
C
A
U
T
I
O
N
When connecting the bypass and load voltage from another model UPS to a Eaton 9395 UPS using the Eaton
Sync Control accessory, use Phase A, Phase B, and Neutral connections from the other UPS. DO NOT connect the
other model UPS Phase C bypass and load voltage to the Sync Control connection point when connecting to an
Eaton 9395 UPS.