INSTALLATION
Eaton 9390 UPS, 9395 UPS, and 9395 SSBM Sync Control Installation and Operation Manual
S
P-164000052 Rev 2
3-2
C
A
U
T
I
O
N
When connecting the bypass and load voltage from another model UPS to an Eaton 9390 UPS using the Eaton
Sync Control accessory, use Phase A, Phase B, and Neutral connections from the other UPS. DO NOT connect the
other model UPS Phase C bypass and load voltage to the Sync Control connection point when connecting to an
Eaton 9390 UPS.
TB1
Ground
Terminal
Figure 3‐1. Typical Eaton Sync Control Wiring Terminal Locations
Содержание Powerware 9390
Страница 1: ...Eaton Powerware 9390 160 N 4x0 Sync Control Ea https eaton power ru catalog eaton 9390 9390 160 n 4x0...
Страница 3: ......
Страница 46: ......
Страница 47: ...P 1640000522 P 164000052 2...