POWER WIRING INSTALLATION NOTES
081505
D
164201554---5
8 of 15
DESCRIPTION:
DATE:
DRAWING NO:
SHEET:
REVISION:
Installation Information
A-19
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
14.
External overcurrent protection is not provided by this product, but is required by codes.
Refer to Table E through Table G for wiring requirements. If an output lockable disconnect
is required, it is to be supplied by the user.
15.
Table K lists the maximum rating for input circuit breakers. When wiring a single-feed input,
the rating requirements for the input circuit breakers are superceded by the ratings listed in
Table L.
Table K. Maximum Input Circuit Breaker Ratings
UPS Model
Input Voltage Rating
208V/220V
480V
Powerware 9390---120/100
Powerware 9390---160/100
80% Rated
450A
200A
100% Rated
350A
150A
Powerware 9390---120/120
Powerware 9390---160/120
80% Rated
500A
225A
100% Rated
450A
175A
Powerware 9390---160/160
80% Rated
700A
300A
100% Rated
600A
250A
C A U T I O N
To reduce the risk of fire, connect only to a circuit provided with maximum input
circuit breaker current ratings from Table K in accordance with the National Electrical
code, ANSI/NFPA 70.
16.
Source protection for the AC input to bypass should be treated as if supplying a 160 kVA
three-phase transformer, to allow for inrush current if an IDC with a transformer is installed.
Bypass input wiring and bypass input breaker rating should be treated as if supplying a
160 kVA load, regardless of the rating of the UPS.
17.
The line-to-line unbalanced output capability of the UPS is limited only by the full load
per phase current values for AC output to critical load shown in Table E through Table G.
The recommended line-to-line load unbalance is 50% or less.
18.
Bypass and output overcurrent protection and bypass and output disconnect switches are
to be provided by the user. Table L lists the maximum rating for bypass and output circuit
breakers satisfying the criteria for both.
Table L. Maximum Bypass and Output Circuit Breaker Ratings
UPS Model
Output Voltage Rating
208V/220V
480V
Powerware 9390---120/100
Powerware 9390---160/100
80% Rated
450A
200A
100% Rated
350A
150A
Powerware 9390---120/120
Powerware 9390---160/120
80% Rated
500A
225A
100% Rated
450A
175A
Powerware 9390---160/160
80% Rated
700A
300A
100% Rated
600A
250A