UPS Operating Instructions
10-6
EATON
Powerware
®
9390 UPS (100–160 kVA) Installation and Operation Manual
S
164201554 Rev E
powerware.com
10.1.9 Using the UPS LOAD OFF Pushbutton
A UPS Load Off is initiated by the
LOAD OFF
pushbutton from the main menu bar or the
System Controls menu bar. This pushbutton can be pressed to control the UPS output. The
UPS
LOAD OFF
pushbutton de-energizes the critical load and powers down the UPS.
The UPS (including Bypass) remains off until restarted.
To use the
LOAD OFF
pushbutton:
1.
Press the
LOAD OFF
pushbutton.
The Load Off screen appears, providing a choice to proceed or abort the
shutdown.
C A U T I O N
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energize the critical load.
2.
To shut down the UPS, press
LOAD OFF
from the Load Off menu bar, and hold for
three seconds. To abort the shutdown, press
CANCEL
.
When LOAD OFF is selected and held for three seconds, the input, output, and
bypass backfeed contactors open, the battery breaker or disconnect is tripped,
and the power module is turned off.
C A U T I O N
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
3.
To restart the UPS after pressing the
LOAD OFF
pushbutton, follow the procedure
in paragraph 10.1.1 or 10.1.2.
W A R N I N G
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is
opened.