Eaton 9355 UPS (20/30kVA) Installation and Operation Manual 164201626—Rev F
www.eaton.com/powerquality
9
Chapter 3
UPS Setup
This chapter describes:
l
Equipment inspection
l
Floor loading and clearances
l
Removing and replacing the cabinet doors
l
Unloading the cabinet(s)
The instructions are intended for the chief operator/system supervisor, electrical consultants, and installation
electricians. Local regulations and electrical code must be followed during the UPS installation.
Inspecting the Equipment
If any equipment has been damaged during shipment, keep the shipping and packing materials for the carrier
or place of purchase and file a claim for shipping damage. If you discover damage after acceptance, file a claim
for concealed damage.
To file a claim for shipping damage or concealed damage: 1) File with the carrier within 15 days of receipt of
the equipment; 2) Send a copy of the damage claim within 15 days to your service representative.
Note:
Check the battery recharge date on the packaging label. If the date has expired and the batteries were
never recharged, do not use the UPS. Contact your service representative.
Floor Loading
When planning the installation, consider the UPS weight for floor loading. The strength of the installation
surface must be adequate for point and distributed loadings. The approximate weights are shown in the
following table.
Clearances
The following clearances are recommended for the Eaton 9355 UPS:
Standard Model Floor Loadings
Eaton 9355
Maximum Weight
Point Loading
20 kVA UPS
1160 lb (526 kg)
290 lb/in
2
(20 kg/cm
2
)
30 kVA UPS
1160 lb (526 kg)
290 lb/in
2
(20 kg/cm
2
)
EBC 36
1160 lb (526 kg)
290 lb/in
2
(20 kg/cm
2
)
EBC 72
2060 lb (934 kg)
515 lb/in
2
(36 kg/cm
2
)
Options Cabinet with
Single Transformer
535 lb (243 kg)
134 lb/in
2
(9.4 kg/cm
2
)
Options Cabinet with
Dual Transformer
792 lb (360 kg)
198 lb/in
2
(13.9 kg/cm
2
)
Options Cabinet with MBS only
205 lb (93 kg)
51 lb/in
2
(3.6 kg/cm
2
)
From Front of Cabinet
36" (91.4 cm) working space
From Back of Cabinet
6" (15.2 cm)
From Right of Cabinet
Refer to local codes for right side service access [minimum 36" (91.4 cm)]