INSTALLATION REFERENCE
EATON
Powerware
®
225 kVA PDU Installation and Operation Manual
S
164201629 Rev D
www.powerware.com
A−2
Table A. Equipment Weight
Component
Rating
kVA
Weight
kg (lb)
Shipping
Installed
Point Loading
PDU
30
474.5 (1045)
445 (980)
4 at 111.3 (245)
50
543.5 (1195)
514 (1130)
4 at 128.5 (282.5)
75
620.5 (1365)
591 (1300)
4 at 147.8 (325)
100
768.5 (1690)
739 (1625)
4 at 184.8 (406.3)
125
804.5 (1770)
775 (1705)
4 at 193.8 (427.3)
150
859.5 (1890)
830 (1825)
4 at 207.5 (456.3)
200
1052.5 (2315)
1023 (2250)
4 at 255.8 (562.5)
225
1143.5 (2515)
1114 (2450)
4 at 278.5 (612.5)
PDU with single front−mounted sidecar
30
604 (1330)
570 (1255)
4 at 142.5 (313.8)
50
673 (1480)
639 (1405)
4 at 159.8 (351.3)
75
750 (1650)
716 (1575)
4 at 179 (393.8)
100
898 (1975)
864 (1900)
4 at 216 (475)
125
934 (2055)
900 (1980)
4 at 225 (495)
150
989 (2175)
955 (2100)
4 at 238.8 (525)
200
1182 (2600)
1148 (2525)
4 at 287 (631.3)
225
1273 (2800)
1239 (2725)
4 at 309.8 (681.3)
PDU with single side−mounted sidecar
30
593 (1305)
559 (1230)
4 at 139.8 (307.5)
50
661 (1455)
627 (1380)
4 at 156.8 (345)
75
739 (1625)
705 (1550)
4 at 176.3 (387.5)
100
886 (1950)
852 (1875)
4 at 213 (468.8)
125
923 (2030)
889 (1955)
4 at 222.3 (488.8)
150
977 (2150)
943 (2075)
4 at 235.8 (518.8)
200
1170 (2575)
1136 (2500)
4 at 284 (625)
225
1261 (2775)
1227 (2700)
4 at 306.8 (675)
NOTE
For each additional front−mounted sidecar, add 130 kg (285 lb) to shipping weight and
125 kg (275 lb) to installed weight.
For each additional side−mounted sidecar, add 118 kg (260 lb) shipping weight and 114 kg (250 lb) to
installed weight.