9PXPPDM1 L2 Receptacle Group
208V:
When the input voltage is 208V, the total output current maximum for the L2 receptacle group is 22.1A.
240V:
When the input voltage is 240V, the total output current maximum for the L2 receptacle group is 22.5A.
CIRCUI
T BREAKER
120V~ 20
A
OUTPU
T 120V~ 20
A
OUTPU
T 120V~ 20
A
CIRCUI
T BREAKER
120V~ 20
A
OUTPU
T 120/240V~ 30
A
OUTPU
T 240V~ 30
A
MAIN
CIRCUI
T BREAKER
240V~ 30
A
T O UPS INPU
T
NORMA
L AC SOURCE
FROM UPS OUTPU
T
(1)
L14-30R
(3)
5-20R
(1)
L6-30R
Figure 28. 9PXPPDM1 L2 Load Output Limits
System Configuration Connections
This section provides illustrations of 9PX PPDM and 9PX Transformer
system configuration connections.
NOTE
The installation diagrams in this section depict rack configurations. Although the
orientation is different, the system connections are the same for tower configurations.
NOTE
Refer to the UPS user's guide for additional installation and system configuration
information.
NOTE
Note the following:
S
For 9PX Transformer configurations, the AC input from the 9PX Transformer
connects to the UPS, then the UPS connects to the Mains.
S
For 9PX PPDM configurations, the AC input of the 9PX PPDM connects to the Mains.
S
For configurations with an MBP or EBM, refer to the appropriate MBP or EBM
user's guide for installation and system configuration information.
Содержание PowerPass 9PXPPDM1
Страница 10: ...INTRODUCTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 4...
Страница 12: ...SAFETY Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 6...
Страница 20: ...EQUIPMENT INSTALLATION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 14...
Страница 40: ...VOLTAGE SELECTION Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 34...
Страница 50: ...STARTUP Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 44...
Страница 54: ...MAINTENANCE BYPASS Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 48...
Страница 62: ...SERVICE AND SUPPORT Eaton 9PXTFMR5 9PXPPDM2 9PXTFMR11 and 9PXPPDM1 User s Guide S P 164000200 Rev 4 56...