30
Instruction Booklet
IB022018EN
Effective July 2020
Instructions for the installation and
EATON
www.eaton.com
Table 4. Relevant standards
Relevant standards
IEC 62271-100
High-voltage switchgear and controlgear - Part 100: Alternating current circuit breakers
IEC 62271-102
High-voltage switchgear and controlgear - Part 102: Hi-voltage alternating current three-position disconnect switches and earthing switches
IEC 62271-200
High-voltage switchgear and controlgears - Part 200: AC metal-enclosed switchgear and control gear for rated voltages above 1 kV and up to and
including 52 kV
IEC 60529
Degrees of protection provided by enclosures (IP code)
IEC 62271-1
High-voltage switchgear and controlgear - Part one: Common specifications
Table 5. Operating conditions
Normal operating conditions, according to IEC 62271 – 1 for indoor switchgear
Ambient air temperature
≤
40° C
≤
35° C on average over 24 hours
≥
-5° C
Altitude
≤
1000 m
Contact Eaton for applications above 1000 m.
Atmosphere
No dust, smoke or corrosive or inflammable gas or vapor, or salt (clean industrial air)
Storage conditions
To retain all of the functional qualities when stored for prolonged periods, we recommend that the equipment be stored in its original packaging,
in well-ventilated, clean, and dry conditions, sheltered from the sun and rain, at a temperature > -25° C and < +55° C.
shows outlines and dimensions for the 1250 A XGIS vertical
section.
shows outlines and dimensions for the 2000 A and 2500 A
XGIS vertical section.