10 Industrial Ethernet Communication Adapter Modules (ECAM)
10.1 EtherNet/IP
86
PXR Electronic trip unit
01/21 MN012005EN
www.eaton.com
Table 48: Real-time data register - EtherNet/IP
Instance
Object
IEEE
floating
point
Fixed
point (FP)
Description
(Values in brackets reflect the American
notation.)
Unit
Scale
factor (FP)
56
182
Cause of status:
High byte = primary status
Low byte = secondary status
–
–
57
183
I
L1
(IA)
A
10
58
184
I
L2
(IB)
A
10
59
185
IL3 (IC)
A
10
60
186
I
G
(IG)
A
10
61
187
I
N
( IN)
A
10
62
188
U
L1-L2
(VAB)
V
10
63
189
U
L2-L3
(VBC)
V
10
64
190
U
L3-L1
(VCA)
V
10
65
191
U
L1-N
(VAN)
V
10
66
192
U
L2-N
(VBN)
V
10
67
193
U
L3-N
(VCN)
V
10
72
198
Active 3-phase power
W
1
73
199
Reactive 3-phase power
Var
1
74
200
Apparent 3-phase power
VA
1
75
201
Power factor
–
100
76
202
Frequency
Hz
10
81
207
Peak active power demand
W
1
82
208
Product ID
–
–
83
209
Frequency
Hz
100
–
210
Active energy (forward)
kWh
1
–
211
Active energy (reverse)
kWh
1
–
212
Active energy combined (= f reverse)
kWh
1
–
213
Apparent energy
kVAh
1
–
214
Active energy (forward)
Wh
1
–
215
Active energy (reverse)
Wh
1
–
216
Active energy combined (= f reverse)
Wh
1
–
217
Apparent energy
VAh
1
84
218
Peak reactive power demand
Var
1
85
219
Peak apparent power demand
VA
1
90
224
Active power demand
W
1
91
225
Reactive power demand
Var
1
92
226
Apparent power demand
VA