CAUTION
All power to the critical load is lost when the LOAD OFF is selected in the following step. You
should use this feature only when you want to de-energize the critical load.
3.
Select LOAD OFF. Command confirmation pop-up screen will show up asking confirmation for the
action. Select YES. The input, output, and bypass backfeed contactors open, the battery breaker or
disconnect is tripped, and all the UPMs are turned off.
4. If another UPS is to be shut down, proceed to that UPS and repeat Steps 1, 2 and 3.
CAUTION
Do not attempt to restart the system after Load Off until the cause of the shutdown has been
identified and cleared.
5.
To restart the UPS after the LOAD OFF, follow the procedure in
Section 7.5.1, Section 7.5.2 or
WARNING
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is
opened and the MOB is opened.
7.5.22 Using the Remote Emergency Power-off Switch
A UPS emergency power-off is initiated by the REPO pushbutton switch. In an emergency, you can use
this switch to control the UPS output. The REPO switch de-energizes the critical load and powers down
the UPSs immediately, without asking for verification.
The UPS, including Bypass, remains off until restarted.
CAUTION
All power to the critical load is lost when the REPO switch is activated in the following step. You
should use this feature only when you want to de-energize the critical load.
NOTE
The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO
switch is used, it may not activate in the same manner; refer to the operating instructions
provided with the switch.
To use the REPO switch:
Содержание Power Xpert 9395P
Страница 1: ...User s and Installation Guide Power Xpert 9395P UPS 500 kVA 600 kVA P 164000476 ...
Страница 2: ...P 164000476 9395P 500kVA 600 kVA 2 Revision 002 User s and Installation Guide ...
Страница 18: ...P 164000476 9395P 500kVA 600 kVA 8 Revision 002 User s and Installation Guide ...
Страница 37: ...P 164000476 9395P 500kVA 600 kVA 27 Revision 002 User s and Installation Guide ...