and may be installed adjacent to the UPS or in a separate location. The recommended installation location for
adjacent battery cabinets is on the right side of the UPS cabinet to allow for future expansion using an external
module.
Consult the
Eaton
®
Power Xpert
®
9395/9395P Integrated Battery Cabinet (Models 1085 and 1085HR)
Installation Manual (P-164000580)
for specifics on battery cabinet usage with the 9395P-600.
11..44..22
FFiieelldd IInnssttaalllleedd U
UP
PM
M
A Field Installed UPM (FI-UPM) provides redundancy for the 9395P-600. The FI-UPM may be installed at any
time in the future. The module cabinet is installed on the left side of the ISBM section and is wired directly to
the UPS. No input or output wiring changes are needed for adding redundancy. Operation remains the same as
the original UPS.
Refer to the
Eaton Power Xpert 9395P UPS Field Installed UPM Mechanical Installation Manual (P-164000503)
for specifics on the FI-UPM usage with the 9395P-600.
11..44..33
S
Syynncc C
Coonnttrrooll
An optional 9395P-600 Sync Control maintains the critical load outputs of two separate single module 9395P-
600 UPS systems in synchronization. This option facilitates the uninterrupted transfer of the load from one load
bus to another by means of transfer switches. The Sync Control is housed in a wall-mounted panel that can be
located between the UPS units for easy wiring.
Refer to the
Eaton
®
Power Xpert
®
9395P Sync Control Installation and Operation Manual (P-164000502)
for
specifics on battery cabinet usage with the 9395P-600.
11..44..44
S
Siinnggllee--FFeeeedd K
Kiitt
An optional kit is available for converting the dual-feed rectifier and bypass inputs to a single-feed configuration.
The kit consists of jumpers and bus bar extensions for each phase, and the hardware required for installation.
Refer to the
Eaton
®
Power Xpert
®
9395/9395P UPS (1000–1200 kVA) Single-Feed Kit Installation Instructions
(P–164000610)
manual for installation instructions.
11..44..55
D
Diissttrriibbuutteedd B
Byyppaassss S
Syysstteem
m
There are two types of redundancy: UPS based (based on the number of UPSs) and UPM based (based on the
number of UPMs).
NOTE
All UPSs in the distributed bypass system must contain the same number of UPMs.
Mixed UPS kVA ratings are not permitted.
A distributed bypass UPS system can be installed to provide a capacity and/or redundant system. This load
sharing system provides more capacity than a single UPS, and can provide backup, depending on the load and
configuration. In addition, when one UPM is taken out of service for maintenance or is not operating properly, a
redundant UPM continues to supply uninterrupted power to the critical load. A Hot Sync Controller Area
Network (CAN) Bridge Card provides connectivity and operational mode control.
The tie cabinet is provided by the customer and must contain Module Output Breakers (MOBs) with dual
auxiliary contacts for control of the system. Without dual auxiliary MOBs, UPMs are not allowed to go to
bypass individually during servicing. All UPMs will go to bypass instead of just the UPM needing service,
decreasing critical load protection. With dual auxiliary MOBs, one UPM can be bypassed while the remaining
UPMs support the load as long as the remaining UPMs have the capacity to do so.
11..44..66
IInnppuutt O
Ouuttppuutt M
Moodduullee C
Coonnffiigguurraattiioonn
The UPS can be supplied in an Input Output Module (IOM) configuration without the bypass input connections,
the static switch, and the backfeed protection contactor. This configuration is primarily used in multiple UPS
parallel systems that do not need a bypass for each UPS and use a separate System Bypass Module (SBM) to
provide system bypass capabilities.
Содержание Power Xpert 9395P-600/600
Страница 8: ......
Страница 122: ...104 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Installation...
Страница 208: ...190 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 UPS Operating Instructions...
Страница 216: ...198 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Communication...
Страница 226: ...16400071007 164000710 07...