Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
207
1100..22..33 U
UP
PS
S EEnnvviirroonnm
meennttaall
Table 51. UPS Environmental
Operating Temperature
All ratings except 600 kW, 300 kW: 0 to 40°C (32 to 104°F) at elevation up to 1000m
without derating.
For 600 kW, 300 kW: 0 to 35°C at elevation up to 1000m without derating.
The recommended operating temperature is 25°C (77°F).
Operating Altitude
Maximum 1000 m (3000 ft) at 40°C without derating
Storage Temperature
–25 to +60°C, excluding batteries (prolonged storage above 40°C causes rapid battery
self discharge)
Relative Humidity (Operating and
Storage)
5% to 95% maximum non-condensing
Agency Markings
78 dB at a 1m distance, A weighted for one UPM UPS
81 dB at a 1m distance, A weighted for two UPM UPS
83 dB at a 1m distance, A weighted for three UPM UPS
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801-2 specifications. Withstands up to 25 kV pulse without damage and with
no disturbance or adverse effect to the critical load.