185
1.
Open the MOB for the UPS being shut down.
2.
On the UPS being shut down, press the
CONTROLS
pushbutton on the main menu bar. The System
Status screen is displayed.
3.
On the System Status screen, select the
BYPASS
command.
4.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
5.
On the Bypass Control Command screen, select
GO TO BYPASS
.
6.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
The UPS being shut down transfer to Bypass mode.
The
BYPASS
status indicator is illuminated. The Bypass status indicates ON. The UPM status indicates
READY
. The power module remains on.
7.
On the System Status screen, select the
UPM
command. The UPS Control Command screen is displayed.
8.
Press the
CONTROLS
pushbutton on the System Status Command menu bar. The UPM 1 Control
Command screen is displayed.
9.
On the UPM 1 Control Command screen, select
UPM OFF
.
10. Press the
SELECT
pushbutton on the UPM 1 Command menu bar. The UPM status indicates
SHUTDOWN
.
The input, output, and battery contactors open, and the power module is turned off.
Logic power remains on.
11. If there are other UPMs in the UPS, they should be shut down in sequence. Repeat Steps 7 through 10
until all other UPMs are shut down.
12. Perform the LOAD OFF procedure in paragraph
Using the UPS LOAD OFF Pushbutton
or paragraph
Using the UPS LOAD OFF Command
on the UPS being shut down.
The input, output, battery, and bypass backfeed contactors open, and the power module is turned off on
the UPS being shut down.
Logic power remains on.
13. Verify the battery breaker or disconnect for the UPS being shut down is open. If not, open the breaker.
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
NOTE
If the UPS contains an input breaker (CB1), DO NOT open the breaker unless no input
feeder breaker is installed.
14. Open the input and bypass feeder circuit breakers for the UPS being shut down.
The UPS is now completely shut down.
External Communications Failure alarm is active on remaining online UPSs. This is an expected event and
will clear upon UPS restart.
77..55..88
S
Siinnggllee U
UP
PS
S R
Reessttaarrtt
To restart a single UPS from a shutdown state:
1.
Close the MOB for the UPS being restarted.
2.
Close UPS input and bypass feeder circuit breakers for the UPS being restarted.
Содержание Power Xpert 9395P-600/600
Страница 8: ......
Страница 122: ...104 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Installation...
Страница 208: ...190 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 UPS Operating Instructions...
Страница 216: ...198 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Communication...
Страница 226: ...16400071007 164000710 07...