74
Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
Figure 24. UPS Intercabinet Interface Harness Locations
UPM Section Left Side View
ISBM Section Right Side View
Output Autotransformer T2
Input Autotransformer T1
44..44..22
C
Coonnnneeccttiinngg IInntteerrccaabbiinneett C
CA
AN
N C
Caabblleess aanndd C
Coonnnneeccttoorrss
NOTE
Four intercabinet interface wiring harnesses are supplied coiled inside the protective
cage on the right side panel of the ISBM section.
1.
In the UPM section, locate the coiled RJ-45 CAN cable. Remove the wire ties securing the cable to the
interior left side panel of the UPM section. Route this cable through the round wiring access in the right
side panel of the ISBM section.
2.
In the ISBM section, locate the J39 inverter CAN connector on the Pl1 interface board and connect the RJ-
45 CAN cable connector to the J39 connector (see
and
).
3.
Dress the interface harnesses and secure in place with wire ties as necessary to prevent wire damage.