70
Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
5.
Remove the screws securing the left top panel and remove the panel (see
). Retain the hardware
for later use.
6.
Remove the screws securing the left middle panel and remove the panel (see
). Retain the
hardware for later use.
Use care during installation to protect components mounted on the right side of the ISBM section and the
intercabinet wiring harnesses attached to the left side UPM section from damage.
ATTENTION!
Lors de l’installation, prendre soin de protéger les composantes du côté droit du module de contournement de
système intégré (ISBM) et les faisceaux de câbles reliant les armoires du côté gauche du module
d’alimentation universel (UPM).
NOTE
Clearance between the ISBM and the UPM sections must be less than 1/2” so that
joining brackets can be installed.
7.
Using a forklift with the forks in the front forklift slots, position the ISBM section adjacent to the left side of
the previously installed UPM section. Verify that the ISBM section right side is against the UPM section
left side and the front of the cabinet bases are flush with each other (see
).
8.
Reinstall the corner channel (see
) and secure using the retained hardware.
9.
Reinstall the left middle panel (see
) and secure using the retained hardware.
Содержание Power Xpert 9395P-600/600
Страница 8: ......
Страница 122: ...104 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Installation...
Страница 208: ...190 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 UPS Operating Instructions...
Страница 216: ...198 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Communication...
Страница 226: ...16400071007 164000710 07...