6
Eaton
®
Power Xpert
®
9395P-600 (300V-600V) Installation and Operation Manual 164000710—Rev 07
NOTE
Startup and operational checks must be performed by an authorized Eaton Customer
Service Engineer, or the warranty terms become void (see Section
). This
service is offered as part of the sales contract for the UPS system. Contact an Eaton
service representative in advance (usually a two-week notice is required) to reserve a
preferred startup date.
11..33
U
UP
PS
S S
Sttaannddaarrdd FFeeaattuurreess
The UPS has many standard features that provide cost-effective and consistently reliable power protection. The
descriptions in this section provide a brief overview of the UPS standard features.
11..33..11
IInnssttaallllaattiioonn FFeeaattuurreess
Each UPS section is shipped separately. The sections are mechanically and electrically joined at the installation
site, and can be permanently bolted to the floor.
Power wiring can be routed through the top or bottom of the cabinet with connections made to easily
accessible terminals. Control wiring is routed through the top of the cabinet and must be installed in
accordance with Class 1 wiring methods.
11..33..22
C
Coonnttrrooll P
Paanneell
The control panel, located on the front of the UPS is a color touchscreen to control the operation of the UPS
and to display the status of the UPS system. See
for additional
information.
11..33..33
C
Cuussttoom
meerr IInntteerrffaaccee
•
Building Alarm Monitoring
. Up to five inputs in the UPS are available to connect the facility's alarm
system contacts. Some system configurations may limit the number of inputs available. The UPS uses
these inputs to monitor the building alarms in addition to the UPS status. See
for additional information.
•
Alarm Contact
. One alarm contact is provided for connection to equipment at the facility, such as a light,
an audible alarm, or a computer terminal. The equipment connected to this contact alerts you to a UPS
alarm. See
for additional information.
•
X-Slot Communication Bays
. Four communication bays are standard equipment. One to four optional X-
Slots inline (for generic slot name; ie: Avaya's alarm adapter) connectivity cards can be installed in the UPS
module at any time. X-Slot cards are quickly installed at the front of the UPS and are hot-pluggable. See
for additional information.
11..33..44
A
Addvvaanncceedd B
Baatttteerryy M
Maannaaggeem
meenntt
A three-stage charging system increases battery service life by optimizing recharge time, and protects batteries
from damage due to high current charging and inverter ripple currents. Charging at high currents can overheat
and damage batteries.
11..33..55
P
Poow
weerr M
Maannaaggeem
meenntt S
Sooffttw
waarree
Intelligent Power Management and Intelligent Power Protector software are available through Eaton support.
See
for additional information.
11..44
O
Oppttiioonnss aanndd A
Acccceessssoorriieess
Contact an Eaton sales representative for information about the following options.
11..44..11
IInntteeggrraatteedd B
Baatttteerryy C
Caabbiinneettss
Battery backup protection can be provided by equipping the UPS system with 9395P-600 battery cabinets
containing sealed lead-acid, maintenance-free batteries. The cabinets are designed for standalone installation
Содержание Power Xpert 9395P-600/600
Страница 8: ......
Страница 122: ...104 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Installation...
Страница 208: ...190 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 UPS Operating Instructions...
Страница 216: ...198 Eaton Power Xpert 9395P 600 300V 600V Installation and Operation Manual 164000710 Rev 07 Communication...
Страница 226: ...16400071007 164000710 07...