69
Figure 6-6. Eaton 9395P
250 kVA / 275 kVA
/ 300 kVA UPS system, 400 V input and 400 V output dual-feed
NOTE
If the load requires a neutral, a bypass source neutral must be provided. If the load does not
require a neutral and there is no neutral conductor connected at the bypass input, a neutral to
ground bonding jumper must be installed. DO NOT install both a source neutral and a bonding
jumper.
9395P 250 kVA / 275 kVA / 300 kVA
User’s and Installation Guide
(Optional)