UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-3
Table 3‐1. UPS Cabinet Maximum Weights
Model
Section
Maximum Weight
kg (lb)
Shipping
Installed
Eaton 9395P-1200/1200
Eaton 9395P-1200/1100
Eaton 9395P-1200/1000
ISBM (CSS)
952 (2099)
908 (2002)
3XUPM
1667 (3675)
1620 (3571)
FI-UPM
500 (1102)
475 (1047)
Eaton 9395P-1200/900
Eaton 9395P-1200/825
Eaton 9395P-1200/750
Eaton 9395P-1200/675
ISBM (CSS)
952 (2099)
908 (2002)
3XUPM
1667 (3675)
1620 (3571)
NOTE
CSS = Continuous Static Switch
The UPS cabinet uses forced air cooling to regulate internal component temperature.
Air inlets are in the front of the cabinet and outlets are in the top. Allow clearance in
front of and above each cabinet for proper air circulation. The clearances required
around the UPS cabinet are shown in Table 3‐2. Dimensions are in millimeters
(inches).
Table 3‐2. UPS Cabinet Clearances
From Top of Cabinet
457.2 mm (18
”
) minimum clearance for ventilation
From Front of Cabinet
914.4 mm (36
”
) working space
From Back of Cabinet
None Required
From Right Side of Cabinet
None Required
From Left Side of Cabinet
None Required
The basic environmental requirements for operation of the UPS are:
S
Ambient Temperature Range:
-
ALL RATINGS EXCEPT 1200 kW, 900 kW: 0–40°C (32–104°F) at elevations up
to 1000m without derating
.
-
For 1200 kW, 900 kW: 0–35°C (32–95°F) at elevations up to 1000m without
derating
S
Recommended Operating Range: 20–25°C (68–77°F)
S
Maximum Relative Humidity:
95%, non-condensing (see section 3.2.1)
NOTE
If Eaton battery cabinets are located in the same room as the UPS, the battery cabinet environmental
requirements supersede the UPS requirements. Operating temperatures above the recommended range will
result in decreased battery life and performance, and will reduce or void the battery warranty. Refer to
Eaton's
Terms and Conditions of Sale with Battery Replacement Coverage