UPS OPERATING INSTRUCTIONS
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
7-28
NOTE
The following instructions are for the Eaton-supplied REPO switch. If a customer-supplied REPO
switch is used, it may not activate in the same manner; refer to the operating instructions provided with the
switch.
To use the REPO switch:
1.
Firmly push the red pushbutton until it locks into place. The switch latches into
the activated state (see Figure 7‐41).
The input, output, and bypass backfeed contactors open, the battery breaker or
disconnect is tripped, and the power module is turned off immediately, without
asking for verification.
C
A
U
T
I
O
N
Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and
cleared.
MISE EN GARDE!
Ne pas tenter de redémarrer le système après le déclenchement du circuit d’arrêt d’urgence à distance avant
d’avoir déterminé la raison du déclenchement.
2.
To deactivate the REPO switch in preparation for restarting the UPS, insert the
supplied key and rotate clockwise until the red pushbutton releases (see
Figure 7‐41). To remove the key, rotate the key back to the vertical position.
3.
Restart the UPS by following the procedure in paragraph 7.4.1.
W
A
R
N
I
N
G
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
A
V
E
R
T
I
S
S
E
M
E
N
T
!
L’intérieur de l’armoire de l’onduleur est alimenté jusqu’à ce que le disjoncteur du circuit d’alimentation en
amont soit activé.
Deactivated
Unlock pushbutton to release
Activated
Pushbutton locked into place
Figure 7‐41. REPO Operation