INTRODUCTION
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
1-5
1.3
Options and Accessories
Contact an Eaton sales representative for information about the following options.
1.3.1
Integrated Battery Cabinets
Battery backup protection can be provided by equipping the UPS system with Eaton
9395P-1200 battery cabinets containing sealed lead‐acid, maintenance‐free batteries.
The cabinets are designed for
standalone
installation and may be installed adjacent to
the UPS or in a separate location. The recommended installation location for adjacent
battery cabinets is on the right side of the UPS cabinet to allow for future expansion
using an external module.
Consult the
Eaton
®
Power Xpert
®
9395 Integrated Battery Cabinet (Model 1085 and
1085HR) Installation Manual (P-164000580)
for specifics on battery cabinet usage
with the Eaton 9395P-1200.
9395PEaton 9395P-1200
.
1.3.2
Field Installed UPM
A Field Installed UPM (FI-UPM) provides upgradability for the Eaton 9395P-1200
Three UPM UPS. The FI-UPM may be installed at any time in the future when power
needs change. The module cabinet is installed on the left side of the ISBM section
and is wired directly to the UPS. No input or output wiring changes are needed for a
capacity increase if the original installation was wired for increased capacity.
Operation remains the same as the original UPS.
1.3.3
Sync Control
An optional Eaton 9395P-1200 Sync Control maintains the critical load outputs of two
separate single module Eaton 9395P-1200 UPS systems in synchronization. This
option facilitates the uninterrupted transfer of the load from one load bus to another
by means of transfer switches. The Sync Control is housed in a wall‐mounted panel
that can be located between the UPS units for easy wiring.
1.3.4
Single-Feed Kit
An optional kit is available for converting the dual-feed rectifier and bypass inputs to a
single-feed configuration. The kit consists of jumpers and bus bar extensions for each
phase, and the hardware required for installation.
1.3.5
Distributed Bypass System
There are two types of redundancy: UPS based (based on the number of UPSs) and
UPM based (based on the number of UPMs). Each UPS contains three or four UPMs.
A distributed bypass UPS system with two to five UPSs can be installed to provide a
capacity and/or redundant system. This load sharing system provides more capacity
than a single UPS, and can provide backup, depending on the load and configuration.
In addition, when one UPM is taken out of service for maintenance or is not operating
properly, a redundant UPM continues to supply uninterrupted power to the critical
load. A Powerware Hot Sync Controller Area Network (CAN) Bridge Card provides
connectivity and operational mode control. The distributed bypass system consists of
two to five UPSs each with a parallel CAN card, and a customer-supplied tie cabinet
or load distribution panel to act as a tie point.
All UPSs in the distributed bypass system must contain the same number of UPMs.
Mixed UPS kVA ratings are not permitted.