Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
45
Table 25. Recommended DC Input Battery Disconnect Ratings – Common Battery
UPS Model
Input Rating for Each UPM
480V/415V/400V/380V
Eaton 9395P-1200/1200
Eaton 9395P-1200/1100
Eaton 9395P-1200/1000
3000A
Eaton 9395P-1200/900
Eaton 9395P-1200/825
2500A
Eaton 9395P-1200/750
Eaton 9395P-1200/675
2000A
Table 26. Recommended DC Input Battery Disconnect Ratings – Separate Battery
UPS Model
Input Rating for Each UPM
480V
480V/415V/400V/380V
Eaton 9395P-1200/1200
Eaton 9395P-1200/1100
Eaton 9395P-1200/1000
Eaton 9395P-1200/900
Eaton 9395P-1200/825
Eaton 9395P-1200/750
Eaton 9395P-1200/675
800A
700A
33..22..55
U
UP
PS
S S
Syysstteem
m IInntteerrffaaccee W
Wiirriinngg P
Prreeppaarraattiioonn
Control wiring for features and options should be connected at the customer interface terminal blocks located
inside the UPS.
Do not directly connect relay contacts to the mains related circuits. Reinforced insulation to the mains is
required.
AVERTISSEMENT!
Ne pas directement brancher les contacts de relais aux circuits du réseau. Une isolation renforcée des réseaux
est nécessaire.
Read and understand the following notes while planning and performing the installation:
•
Use Class 1 wiring methods (as defined by the NEC) for interface wiring from 30V to 600V. The wire
should be rated at 600V, 1A minimum and 12 AWG maximum.
•
Use Class 2 wiring methods (as defined by the NEC) for interface wiring up to 30V. The wire should be
rated at 24V, 1A minimum. When Class 2 circuit wiring must be mixed with Class 1 wiring, use Class 1
wire and wiring methods.
•
Use shielded twisted-pair wires for each input and return or common.
•
All interface wiring and conduit is to be provided by the customer.
Содержание Power Xpert 9395P-1100/1100
Страница 8: ......
Страница 28: ...10 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Introduction...
Страница 112: ...94 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS System Installation...
Страница 154: ...136 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Understanding UPS Operation...
Страница 202: ...184 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Communication...
Страница 210: ...192 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS Maintenance...
Страница 214: ...16400050011 164000500 11...