Table 17. Supplied Intercabinet Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part
Number
Flat Washer
M8
36
UPM AC Input, UPM Battery Input,
UPM AC Output
180500036-080
Conical Washer
M8
36
UPM AC Input, UPM Battery Input,
UPM AC Output
180500037-080
Nut
M8
36
UPM AC Input, UPM Battery Input,
UPM AC Output
180200001-05
Terminals E1 through E11 are 2-hole busbar mountings for standard NEMA 2-hole barrel lugs. The power wiring
connections for this equipment are rated at 90°C. See
for power cable terminations,
for
supplied terminal hardware, and
for recommended installation parts and tools not supplied by Eaton.
through
show the location of the power cable terminals inside the UPS.
Table 18. UPS External Power Cable Terminations for Three/Four UPM Models
Terminal Function
Terminal
Function
Bus Landings (using
both sides of bus)
Tightening Torque
Nm (lb ft)
Bolt Size
AC Input to UPS Rectifier
E1
Phase A
8 – 2 bolt mounting
76 (56)
M12
E2
Phase B
8 – 2 bolt mounting
76 (56)
M12
E3
Phase C
8 – 2 bolt mounting
76 (56)
M12
AC Input to Bypass
E6
Phase A
6 – 2 bolt mounting
76 (56)
M12
E7
Phase B
6 – 2 bolt mounting
76 (56)
M12
E8
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Output to Critical Load
E9
Phase A
8 – 2 bolt mounting
76 (56)
M12
E10
Phase B
8 – 2 bolt mounting
76 (56)
M12
E11
Phase C
8 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
– Common Battery
E4
Battery (+)
16 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
16 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
– Separate Battery (UPM 1)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
– Separate Battery (UPM 2)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS
– Separate Battery (UPM 3)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
Содержание Power Xpert 9395P-1100/1100
Страница 8: ......
Страница 28: ...10 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Introduction...
Страница 112: ...94 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS System Installation...
Страница 154: ...136 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Understanding UPS Operation...
Страница 202: ...184 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Communication...
Страница 210: ...192 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS Maintenance...
Страница 214: ...16400050011 164000500 11...