44
Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings
from
in accordance with the NEC, ANSI/NFPA 70.
ATTENTION!
Pour réduire le risque d’incendie, ne brancher qu’à un circuit avec le courant nominal maximal du disjoncteur
d’entrée indique dans le tableau (
) conformement à la norme ANSI/ NFPA 70 du NEC.
Table 24. Recommended Bypass, Output, and MOB Circuit Breaker Ratings (100% and 80% Load Rating)
UPS Model
Input Rating
%
480V
415V
400V
380V
Eaton 9395P-1200/1200
100
1600A
N/A
N/A
N/A
80
2000A
N/A
N/A
N/A
Eaton 9395P-1200/1100
100
1600A
1600A
1600A
2000A
80
2000A
2000A
2000A
2500A
Eaton 9395P-1200/1000
100
1600A
1600A
1600A
1600A
80
1600A
2000A
2000A
2000A
Eaton 9395P-1200/900
100
1200A
1600A
1600A
1600A
80
1600A
2000A
2000A
2000A
Eaton 9395P-1200/825
100
1000A
1200A
1200A
1600A
80
1600A
1600A
1600A
1600A
Eaton 9395P-1200/750
100
1000A
1200A
1200A
1200A
80
1200A
1600A
1600A
1600A
Eaton 9395P-1200/675
100
1000A
1000A
1000A
1200A
80
1200A
1200A
1600A
1600A
NOTE Bypass conduit data is not applicable to IOM configurations.
There is no manual DC disconnect device within the UPS.
A battery disconnect switch is required for battery systems and may also be required by NEC or local codes.
The battery disconnect switch should be installed between the battery and the UPS.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is
computed at 2 volts per cell.
The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of
nominal DC voltage at rated battery current.
External DC input overcurrent protection and disconnect switch is to be provided by the customer.
and
list the maximum ratings for continuous–duty rated circuit breakers satisfying the criteria for both.
Recommended disconnect size is based on a maximum full load discharge time less than 3 hours. For longer
discharge times a larger disconnect may be required.
Содержание Power Xpert 9395P-1100/1100
Страница 8: ......
Страница 28: ...10 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Introduction...
Страница 112: ...94 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS System Installation...
Страница 154: ...136 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Understanding UPS Operation...
Страница 202: ...184 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Communication...
Страница 210: ...192 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS Maintenance...
Страница 214: ...16400050011 164000500 11...