Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
43
Table 22. 415V /400V/380V Power Cable Conduit Requirements (Continued)
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
Number of
Conduits
All models
DC
(Separate Battery -
per UPM)
Battery
(Positive, Negative, Ground)
7
4
1
NOTE 1 Because of the future upgradability to a fully rated 415V 825 kVA UPS with the addition of the FI-UPM, these conduit sizes
are specified for an 825 kVA UPS.
NOTE 2 Bypass conduit data is not applicable to IOM configurations.
Battery Conductor Routing
: Refer to the notes at the bottom of
to
Input/Output Ratings and External Wiring
Requirements.
External overcurrent protection and disconnect are not provided by this product, but are required by codes.
Refer to Refer to
,
, or
for wiring requirements. If an output lockable disconnect
is required, it is to be supplied by the customer.
The values are the same for 480V, 415V, 400V, and 380V input circuit breakers with 100% breaker ratings for
rectifier input (see
).
NOTE
For the Eaton 9395P-1200 400/415/380V models, the max output is 1100 kW / 1100
kVA.
Table 23. Recommended Input Circuit Breaker Ratings (100% and 80% Load Rating)
UPS Model
Input Rating
%
480V
415V
400V
380V
Eaton 9395P-1200/1200
100
2000A
N/A
N/A
N/A
80
2500A
N/A
N/A
N/A
Eaton 9395P-1200/1100
100
1600A
2000A
2000A
2000A
80
2000A
2500A
2500A
2500A
Eaton 9395P-1200/1000
100
1600A
2000A
2000A
2000A
80
2000A
2500A
2500A
2500A
Eaton 9395P-1200/900
100
1600A
1600A
1600A
1600A
80
2000A
2000A
2000A
2000A
Eaton 9395P-1200/825
100
1600A
1600A
1600A
1600A
80
1600A
2000A
2000A
2000A
Eaton 9395P-1200/750
100
1200A
1600A
1600A
1600A
80
1600A
2000A
2000A
2000A
Eaton 9395P-1200/675
100
1200A
1200A
1200A
1200A
80
1600A
1600A
1600A
1600A
Содержание Power Xpert 9395P-1100/1100
Страница 8: ......
Страница 28: ...10 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Introduction...
Страница 112: ...94 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS System Installation...
Страница 154: ...136 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Understanding UPS Operation...
Страница 202: ...184 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Communication...
Страница 210: ...192 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS Maintenance...
Страница 214: ...16400050011 164000500 11...