Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
7
11..44
B
Baatttteerryy S
Syysstteem
m
Although not provided with the UPS, a battery system is required to provide emergency short-term backup
power to safeguard operation during brownouts, blackouts, and other power interruptions. The battery system
should be equipped with lead–acid batteries. An external battery disconnect switch must be used.
The UPMs may be powered with either a common or separate battery system. In a common battery system,
single and multiple UPMs are powered from one common battery source. In a separate battery system,
multiple UPMs are each powered from separate battery sources.
UPMs in distributed bypass and parallel systems must use a separate battery system.
Consult the
Eaton
®
Power Xpert
®
9395/9395P Integrated Battery Cabinet (Model I085 and 1085HR) Installation
Manual (P-164000580)
for specifics on battery cabinet usage with the 9395P-1200.
A supplemental 48 Vdc shunt trip signal for the battery disconnect device is provided by the UPS, but is not
required for normal operation.
NOTE
The Eaton 9395P-1200 system can trip a maximum of six battery cabinets total. This
applies to both the 1085 standard and High Rate series batteries. If more than six
battery cabinets in total are needed in a separate UPM battery configuration, DO NOT
hook up the shunt trips.
11..55
U
Ussiinngg TThhiiss M
Maannuuaall
This manual describes how to install and operate the Eaton 9395P-1200 (1200 kVA, 1200 kW) UPS. Read and
understand the procedures described in this manual to ensure trouble-free installation and operation. In
particular, be thoroughly familiar with the REPO procedure (see paragraph ).
The information in this manual is divided into sections and chapters. The system, options, and accessories
being installed dictate which parts of this manual should be read. At a minimum, Chapters 1 through 4 and
Chapter 7 should be examined.
Read through each procedure before beginning the procedure. Perform only those procedures that apply to the
UPS system being installed or operated.
11..66
C
Coonnvveennttiioonnss U
Usseedd iinn TThhiiss M
Maannuuaall
This manual uses these type conventions:
•
Bold type
highlights important concepts in discussions, key terms in procedures, and menu options, or
represents a command or option that you type or enter at a prompt.
•
Italic type
highlights notes and new terms where they are defined.
•
Screen type
represents information that appears on the screen or LCD.
Icon
Description
Information notes call attention to important features or instructions.
[Keys]
Brackets are used when referring to a specific key, such as [Enter] or [Ctrl].
In this manual, the term
UPS
refers only to the UPS cabinet and its internal elements. The term
UPS
system
refers to the entire power protection system – the UPS cabinet, the battery cabinet, and options or
accessories installed.
Содержание Power Xpert 9395P-1100/1100
Страница 8: ......
Страница 28: ...10 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Introduction...
Страница 112: ...94 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS System Installation...
Страница 154: ...136 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Understanding UPS Operation...
Страница 202: ...184 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Communication...
Страница 210: ...192 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS Maintenance...
Страница 214: ...16400050011 164000500 11...