The input, output, battery, and bypass backfeed contactors open, and the power module is turned off.
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
3.
If the UPSs contain input breakers (CB1), open all UPS input breakers.
4.
Open the input and bypass feeder circuit breakers on all UPSs.
77..55..1100 C
Chhaarrggeerr C
Coonnttrrooll
To turn on the battery charger:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
CHARGER
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Charger Control Command screen
is displayed.
4.
On the Charger Control Command screen, select
CHARGER ON
.
5.
Press the
SELECT
pushbutton on the Charger Command menu bar.
To turn the battery charger off:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
CHARGER
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Charger Control Command screen
is displayed.
4.
On the Charger Control Command screen, select
CHARGER OFF
.
5.
Press the
SELECT
pushbutton on the Charger Command menu bar.
77..55..1111 U
Ussiinngg tthhee U
UP
PS
S LLO
OA
AD
D O
OFFFF P
Puusshhbbuuttttoonn oorr C
Coom
mm
maanndd
A UPS Load Off is initiated by the
LOAD OFF
pushbutton from the main menu bar, the Load Off command on
the UPS Control Command screen, or the Load Off command on the Bypass Control Command screen. The
UPS
LOAD OFF
controls the UPSs' outputs by powering down the UPS and de–energizing the critical load.
NOTE
The UPS Load Off controls each UPS independently and does not shut down the whole
distributed bypass system unless all UPSs have been transferred to bypass. To
immediately shut down the whole system, use the REPO switch (see paragraph
Using the Remote Emergency Power-off Switch
To use the
LOAD OFF
pushbutton:
1.
Press the
LOAD OFF
pushbutton on the UPS to shut down.
The Load Off screen is displayed, providing a choice to proceed or abort the shutdown.
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de–energize the critical load.
2.
To shut down the UPS, press
LOAD OFF
from the Load Off menu bar, and hold for three seconds. To
abort the shutdown, press
CANCEL
.
Содержание Power Xpert 9395P-1100/1100
Страница 8: ......
Страница 28: ...10 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Introduction...
Страница 112: ...94 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS System Installation...
Страница 154: ...136 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Understanding UPS Operation...
Страница 202: ...184 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 Communication...
Страница 210: ...192 Eaton Power Xpert 9395P 1200 Installation and Operation Manual 164000500 Rev 11 UPS Maintenance...
Страница 214: ...16400050011 164000500 11...