Eaton
®
Power Xpert
®
9395P-1200 Installation and Operation Manual 164000500—Rev 11
109
Figure 58. Supervisory Contact Module II TB2
System Normal
No Redundancy
On Generator
Bypass Not Available
On Battery
UPS Alarm
On Bypass
Shutdown Imminent
NOTE
Supervisory contacts are rated at 2.0A at 28 Vdc or 120 Vac and 0.15A at 115 Vdc.
NOTE
Supervisory contacts require an external power supply. Internal 24 Vdc is not capable of
supplying contact current.
55..66
A
Acccceessssoorryy M
Moouunnttiinngg D
Diim
meennssiioonnss
through
show the dimensions of the RMP II, the RIM II, and the SCM II.