![Eaton Power Xpert 9395 UPS Скачать руководство пользователя страница 177](http://html1.mh-extra.com/html/eaton/power-xpert-9395-ups/power-xpert-9395-ups_installation-and-operation-manual_3950068177.webp)
UPS Operating Instructions
Power Xpert
TM
9395 UPS (450–825 kVA) Installation and Operation Manual 164201725—Rev 10
www.eaton.com/powerquality
7-15
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4.
On the UPS Control Command screen, select
START HIGH ALERT
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS starts High Alert mode with the UPMs online supplying the critical load. After one hour the UPS
transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates
HIGH ALERT
. The UPM status
indicates
ONLINE
. The power module is on.
7.3.5
Enable Variable Module Management System Mode from the UPS Command Menu
To enable Variable Module Management System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4.
On the UPS Control Command screen, select
ENABLE VAR MODULE MANAGEMENT
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS transfers to Variable Module Management System mode. In approximately twenty seconds the
UPS calculates the required number of UPMs needed to support the load.
The Online status indicator is illuminated. The UPS status indicates
VMMS
. The UPM status
indicates
ONLINE
.
7.3.6
Disable Variable Module Management System Mode from the UPS Command Menu
To disable Variable Module Management System mode:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4.
On the UPS Control Command screen, select
DISABLE VAR MODULE MANAGEMENT
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS transfers to Battery mode and then to Online mode in approximately ten seconds.
NOTE
The Variable Module Management System mode commands are displayed only if
enabled at the factory or by an Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable
Module Management System mode commands will not be displayed.
NOTE
The Variable Module Management System mode commands are displayed only if
enabled at the factory or by an Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Energy Saver System mode is enabled, the Variable
Module Management System mode commands will not be displayed.
Содержание Power Xpert 9395 UPS
Страница 2: ......
Страница 27: ...Installation ...
Страница 28: ......
Страница 123: ...Section 2 Operation ...
Страница 124: ......
Страница 249: ......
Страница 250: ... 164201725 10 164201725 10 ...