UPS System Installation
Power Xpert
TM
9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716—Rev 8
www.eaton.com/powerquality
4-17
Figure 4-12. Interface Terminal Locations
X-Slot Communication Bays
TB3
TB1 and TB2
(See Figure 4
‐
13 for detail.)
(See Figure 4
‐
15 for
terminal assignments.)
(See Figure 4
‐
18 for detail.)
Table 4-1. TB1, TB2, and TB3 Interface Connections
Terminal TB1
Name
Description
1
REPO NC
I
nput: Normally
closed dry contact used to activate UPS EPO from a remote switch.
2
REPO Return
3
REPO NO
I
nput: Normally
open dry contact used to activate UPS EPO from a remote switch.
4
REPO Return
5
Battery Aux
Input: Normally
open contact used to indicate when UPS battery breaker is open or closed.
6
Battery Aux Common
7
48 Vdc Battery Shunt Trip +
Output: Contacts used to open battery breaker or disconnect.
8
48 Vdc Battery Shunt Trip
9
Output Contactor K3 NC Aux
Output: Normally
closed contact opens when output contactor closes.
10
Output Contactor K3 NC Aux Common