6
Installation Instructions – LDRT8B/LDRT812B Commercial Recessed LED Retrofit
Installation Instructions – LDRT8B/LDRT812B Commercial Recessed LED Retrofit
IB520052EN www.eaton.com
Electrical Connection
CAUTION
Make certain no bare wires are exposed outside of wire nut
connectors.
1. Provide electrical service according to the “National
Electrical Code” or your local electrical code to the
junction box (located on the plasterframe). Supply wire
insulation must be rated for at least 90°C. The junction
box is rated for a maximum of 8 No. 12 AWG Branch
Circuit conductors and is also suitable for at least 90°C
2. Remove junction box cover (Figure 41).
3. Remove appropriate round pryout and connect conduit
to junction box with proper connector (not included).
4. Connect supply lead wires to junction box lead wires
(line, neutral and ground) in the fixture using the
provided lever nut connectors. (Figure 43). Be careful
not to leave any bare conductors outside of the lever
nut connectors.
5. Lift the orange tab on the lever nut to disengage the
wire and close to secure the wire in place. (Figure 43).
6. Connect white to white, black to black, and green
(from electrical service) on the supply side to the bare
copper wire in the junction box. Place all excess wiring
and connections into the junction box and replace the
cover. Place all connections and excess wiring into the
junction box and replace cover.
Figure 38
Figure 39
Figure 40
Cleaning
To Clean Trims:
1. Gently wipe with soft, clean, dry lint-free cloth to
remove dust.
2. Wipe with mild detergent solution on a soft, clean
cloth to remove fingerprints and stains.
3. Rinse with clean water and dry with soft, clean, dry lint-
free cloth.
Figure 37