Execute the following inspections as soon as possible upon arrival of your Eaton equipment:
1.
Open the front door and check the nameplate on the cabinets to verify that the model numbers correspond
with the ones specified on the bill. Record the model and serial numbers for service reference.
2.
The installer should open doors, remove the internal panels, and check for any damage that may have
occurred during shipment. Check for loose connections or unsecured components as listed in the
following section.
33..33..11
IInntteerrnnaall W
Wiirriinngg IInnssppeeccttiioonn
!
IMPORTANT
The Installer should review the STS for connections and safety prior to final positioning and
installation.
The installer should perform a visual inspection to verify that lug connections have not come loose, as follows:
1.
Check these connections to make sure vibration has not loosened the terminal screws.
a.
Input source and MCSWs
b.
Bypass MCSWs
c.
Isolation MCSW(s)
2.
Check all lugs on the following:
a.
Neutral Bus
b.
Ground Bus
c.
Bus bars
d.
Switches and circuit breakers
e.
SCR switch modules
If loose connections are found during the installation, contact Eaton Help Desk, see paragraph
for contact information.
Содержание PDI WaveStar TFA STS 250-600A
Страница 4: ......
Страница 16: ...2 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Safety ...
Страница 120: ...106 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Web Pages ...
Страница 124: ...110 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Troubleshooting ...
Страница 149: ...Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 135 Resources ...
Страница 150: ...P 16400111301 P 164001113 01 ...