Coooolliinngg
TFA STS 250A-1200A units use forced air cooling with redundant fans and reject heat through ventilation
openings.
22..88
O
Oppeerraattiioonnaall IInnffoorrm
maattiioonn aanndd C
Coonnttrroollss
The TFA STS has a color graphics touchscreen, a backup operator interface (the ROI), help screens, and audible
voice assistance that supplements the display in certain situations.
22..88..11
G
Grraapphhiiccss TToouucchh--S
Sccrreeeenn M
Moonniittoorr//D
Diissppllaayy
The STS has a front touchscreen display that can display the following information:
•
A dynamic one-line mimic display, showing the active source-to-output path, bypass, and measurements
(See
).
•
Setup and configuration settings
•
Administrative and operational controls
•
Alarm Log and Event Log
•
AC wave form capture for transfer events or displaying the current wave structure
•
Digital and Analog Points (Modbus registers)
•
Voltage and current measurements for input sources and output load
•
Harmonics for both voltage and current
•
Load trending
22..88..22
O
Oppeerraattiioonnaall A
Assssiissttaannccee
•
The Voice Unit annunciates alarms ("Static switch, new alarm") and cleared alarms at the unit and provides
operator cautions ("You are not authorized for this function").
•
The Help function provides both text and voice-over instructions to guide operators through transfer tasks
for going to Bypass Mode and returning from Bypass to Normal Mode. The instructions are context-
specific, providing information for transfers appropriate to the current STS source-to-output connections.
22..99
S
Syysstteem
m S
Seeccuurriittyy
The TFA STS is designed for mission-critical environments and has security features appropriate to that
environment:
•
The administrator assigns each user a unique Personal Identification Number (PIN) associated with an
access level, such as administrator or operator, determining what actions the user can perform.
•
A PIN and password are required to login.
•
No changes to system parameters or STS operation can be made through the touchscreen Monitor
without a valid user login, and no changes at all can be made remotely via web access.
•
Only one user can be logged in at a time. The Event Log records and time-stamps the user’s login,
changes to parameters or actions while the user is logged in, and the user’s logout.
•
A key is required to open doors, controlling access to the MCSWs and components. Key access is also
required for the ROI.
•
When an STS front door is opened, the unit alarms and the alarm is logged into the Event Log.
Содержание PDI WaveStar TFA STS 250-600A
Страница 4: ......
Страница 16: ...2 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Safety ...
Страница 120: ...106 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Web Pages ...
Страница 124: ...110 Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 Troubleshooting ...
Страница 149: ...Eaton PDI WaveStar TFA Static Transfer Switch Installation and Operation Manual P 164001113 Rev 01 135 Resources ...
Страница 150: ...P 16400111301 P 164001113 01 ...